S series of PC-class Dual-supply Automatic Switch

(Hereinafter ATSE)

General

  • S series of PC-class dual-power supply automatic switch (hereinafter ATSE) is the latest company Technology development of high-tech products. It is in line with GB/T14048.1-2006, GB/T14048. 11-2002 superscript, And also with "high-rise buildings fire norms" and "Architectural Design fire norms", "emergency Lighting Design Guide, "" civil electrical design specifications. " Product component, parts after martial law Screening of the aging grid, finished a continuous 168 hours of electricity a dry run, the final pass through the test load Before the factory. This is t o ensure the product's reliability and security.
  • ATSE apply to AC 660 V, rated frequency of 50 Hz/60Hz. 250 volts DC and the following Occasion.
  • The products are mainly used for the state of a load, widely applicable to the fire, postal communication,hospitals, hotels, Urban rail transport and high-rise buildings, industrial assembly line, television stations need electricity for the important parts. Main power Emergency Power can be power grids, with Self-excitation generator sets, battery, and so on.

Working Conditions

  • Ambient air temperature Ambient air temperature of -15℃to +60℃, and a 24-hour average temperature does not exceed +55℃. Around +65℃ air temperature is above or below -20℃ users should consult with the manufactures.
  • Atmospheric humidity The maximum temperature of +40℃ the relative humidity of not more than 50 percent, the largest of 90% relative humidity, ability Humid air by the impact of the sea, at a lower temperature may allow a higher relative humidity, Occasionally the temperature under Congeal Dew should take special measures.
  • Installation Altitude Location on the place no more than 2,000 meters above the sea level. For a higher altitude, taking into account the air Xinhua strength and cooling down, in consultation with the Manufacturer.
  • Pollution levels Installation on grade III
  • Installation sort Installation sort IV type
  • Installed tilt Products in the cabinet fixed installation, the largest inclination to ±22.5
  • Flash Arc-distance In AC 380 V-arc distance of 80 mm. AC at 660 V-arc distance of 100 mm. Under 125A installation do not consider flash arc.
  • Use category AC-33B

The model of PC class ATS and it's meaning

Switch Parameter

Note:

  • 1). The weight listed only for reference
  • 2). Short time current, operate current and jump current are all for reference.

The controler wiring diagram of standard three section of YES1-S type

The wiring diagram of two section of YES1-L/II type transfer at once

YES1-S , YES1-L Type ATS appearance and Installation Dimension

  • The safe distance dimensions of the panel: 30mm(400V), 60mm(690V)
  • Note: the dimensions with '' * '' only can be equipped with YCU-LⅠ controller
  • The safe distance dimensions of the panel: 30mm(400V), 60mm(690V)
  • Note: the dimensions with '' * '' only can be equipped with YCU-LⅠ controller

The method of manual operating and note

  • 1. the manner of A power input: Screwdriver press the "two-way power off, so A, B are in the off position of power(YES1-Ltwo section no need this operation), With a wrench to manually rotate the direction of the arrow shaft so that the power A will place in ON position
  • 2. the manner of B power input: Screwdriver press the "two-way power off, so A, B are in the off position of power(YES1-Ltwo section no need this operation), Then press the "power B-oriented" and to maintain,while manually rotating the direction of the arrow shaft, so that the power Bwill place in ON position
  • 3. the manner of Artificial escape:(only fit for YES1-S three section,YES1-L can only transfer can not release ) Remove manual operating handle ,to the left of screwdriver insert "two-way power off" and the hole can escape to the internal pressure
  • Note : The manual was forbiddened when Switch with load conditions, manual operationis allowed when the controller must be in manual or power-off state

The function of brief type controller

  • Detection of two-way power supply to see if there is power, power loss with voltage detection function (only single phase)
  • Call instructions with power, power input status indicators
  • Self-input and self-recover or Self-input andwithout self-recover can choose by the customer
  • Main and standby all have the function of time delay,and the delay time can be adjusted between 0-25s
  • The switch body integration through plug terminals installed
  • If is fit for the ATS with the current below 500Amp
  • If is fit for the ATS with the current below 500Amp Brief type controller either fit for two section YES1-L type or three section YES1-S type .Only has the function of transfer automatically without the function of double point.

The Technical parameters of brief type controller:

  • Working power: 175V-260V
  • Power Consumption:<3W
  • Working temperature/ Storage temperature:-10℃ to 50℃/ -20℃to 70℃
  • Weight:200g
  • The on-off parameters of the relay: 250V 5A AC power , Positive load
  • Protection class: IP20

Conversion time adjustment parameter table:

Note: the 4 switch on the right side to the position of "self-recovery", reset automatically when the normal A power supply